SRF Water System Upgrades
BID DATE
09/3/26 - 7:00
AGENCY
Green Cove Springs
ESTIMATE
n/a
SCOPE
Remove and replace two Jockey and three High Service (HS) Pumps to increase available service pressure to Magnolia Point. Revised design points are summarized as follows: Jockey Pumps: 400 gpm @ 196 ft (TDH) | 85 psig HS Pumps: 1,200 gpm @ 196 ft (TDH) | 85 psig Magnolia Point Loop Control Station 1 and Station 2 valving modifications to remove existing hydraulic control valves with motor-operated butterfly valves. Harbor Road Elevated Storage Tank (EST) hydraulic altitude valve removal and replacement with motor operated butterfly valves. Associated electrical and instrumentation improvements. Bonaventure EST Improvements: Hydraulic altitude valve removal and replacement with motoroperated butterfly valves. https://procurement.opengov.com/portal/greencovesprings/projects/285754